AC Installation Two-Story Home — Taylorsville Case Study

Before and after

Oversized 3.5-ton AC condenser at 1998 Taylorsville home before Aegis right-sizing
Before: Oversized 3.5-ton AC condenser at 1998 Taylorsville home before Aegis right-sizing
New right-sized 2.5-ton two-stage AC installed by Aegis at Taylorsville two-story home
After: New right-sized 2.5-ton two-stage AC installed by Aegis at Taylorsville two-story home

A Taylorsville customer in a 1998-built two-story home contacted us about replacing their aging AC. The existing 15-year-old AC was past typical service life and showing capacity decline, and the customer experienced the classic two-story comfort imbalance — upstairs uncomfortably warm during summer despite the AC running constantly.

This case study documents an AC installation paired with two-zone system integration that addressed both equipment replacement and comfort imbalance simultaneously.

Customer Situation

  • Home: 1998-built Taylorsville two-story, approximately 2,400 sq ft (1,300 sq ft main level, 1,100 sq ft upper bedroom level)
  • Existing equipment: 15-year-old Goodman R-410A AC, 3.5 ton; 96% AFUE furnace from 2018 (not being replaced)
  • Symptom: AC running constantly during summer with upstairs 6–8°F warmer than thermostat (located on main level)
  • Customer priorities: Address comfort imbalance, reasonable cost, avoid oversized equipment

Manual J Load Calculation

On-site Manual J with per-zone analysis:

  • Total cooling load: 32,000 BTU/h (2.67 tons)
  • Main level zone: 17,000 BTU/h
  • Upper level zone: 15,000 BTU/h

Note: existing 3.5 ton AC was 31% oversized for actual load — common scenario producing short-cycling and poor dehumidification.

Equipment and Project Selection

Recommended approach: Two-stage 16 SEER2 AC paired with two-zone system

  • Trane XR16 2.5 ton two-stage AC (right-sized vs. oversized 3.5 ton existing)
  • Honeywell HZ322 two-zone control panel
  • Zone dampers in supply trunk
  • Bypass damper for excess airflow management
  • Two Ecobee Smart thermostats

Project cost: $12,400

The existing 2018 furnace has variable-speed ECM blower which integrates properly with two-stage AC and zoning — no furnace modifications needed.

Installation

Duration: 1.5 days

Day 1: AC equipment installation – R-410A recovery from old equipment per EPA – Old condenser and evaporator coil removal – New evaporator coil installation in furnace plenum – New outdoor condenser placement on existing pad – Refrigerant line work with nitrogen purge during brazing – System evacuation to 425 microns – R-410A charge by weight

Day 2 (half day): Zoning installation and commissioning – Zone damper installation in supply trunk – Bypass damper installation – Zone control panel installation – Thermostat installations (main level and upper level) – Low-voltage wiring – Complete commissioning

Commissioning Measurements

AC operation: – Outdoor temperature: 87°F – Suction pressure: 134 psi ✓ – Discharge pressure: 348 psi ✓ – Subcool: 10°F ✓ – Temperature differential: 19°F ✓ – Compressor amp draw stage 2: 10.8 amps ✓

Zoning verification: – Main only call: zone 1 open, zone 2 closed, bypass partially open – Upper only call: zone 2 open, zone 1 closed, bypass partially open – Both zones: dampers open, bypass closed – AC stage 1 operates during single-zone calls – AC stage 2 engages during both-zone high-demand periods

Final Cost and Rebate Filing

Customer’s project cost: $12,400

Rebates filed: – Federal 25C tax credit: $600 – Rocky Mountain Power Wattsmart AC rebate: $150

Effective net cost after incentives: $11,650

Customer Outcome

Summer performance comparison:

Metric Old AC New AC + Zoning
Main level temperature 74°F 74°F
Upper level temperature 80°F 74°F
Indoor humidity 58% 48%
Average daily run time 14 hours 9 hours
Average summer electric bill $245/mo $185/mo

Customer assessment: Comfort imbalance eliminated. Significant energy savings ($60/month average summer). Two-stage equipment quieter than old single-stage.

What This Case Study Demonstrates

  • Two-story comfort imbalance solved by zoning, not equipment oversizing
  • Right-sized 2.5 ton AC outperforms oversized 3.5 ton equipment
  • Two-stage AC + zoning integration delivers efficiency AND comfort
  • Existing variable-speed furnace compatible with zoning installation
  • Significant energy savings ($60/month) plus comfort improvement

Considering Similar Project?

If you have two-story comfort imbalance in your Taylorsville home, call (385) 250-0687.

  • Phone: (385) 250-0687
  • Address: 4454 Manhattan Ct, West Valley City, UT 84120

See AC Installation in Taylorsville →

Who does this work: Aegis Heating and Air’s own W-2 crew — 3 NATE-certified technicians and 6 EPA 608 Universal field technicians, no subcontractors. Utah DOPL S350 License 7482916-5501. Meet the team · Our warranty · (385) 250-0687

Aegis services in Taylorsville

AC repair · AC installation · Furnace repair · Furnace installation · Heat pumps · Ductless mini-splits · Maintenance · Indoor air quality · Commercial HVAC · Emergency HVAC · All of Taylorsville