Zoned HVAC System Install — Taylorsville Case Study

Before and after

Original single-zone trunk duct at 2008 Taylorsville home before three-zone retrofit
Before: Original single-zone trunk duct at 2008 Taylorsville home before three-zone retrofit
Three-zone system with bypass damper installed by Aegis at Taylorsville home
After: Three-zone system with bypass damper installed by Aegis at Taylorsville home

A Taylorsville customer in a 2008-built two-story home with a finished basement contacted us about adding zoning to their existing HVAC system. The home had three distinct comfort areas — main level (kitchen, living, dining), upper bedroom level, and finished basement — each with different cooling and heating needs based on use patterns, solar exposure, and occupancy. Single-zone HVAC produced comfort complaints across all three areas at different times of day. This case study documents a three-zone retrofit installation that addressed the multi-area comfort challenges.

Customer Situation

  • Home: 2008-built Taylorsville two-story with finished basement, approximately 3,200 sq ft total
  • Existing equipment: 2008 Trane 96% AFUE furnace, 2008 Trane 16 SEER AC, both still functional
  • Symptom: Main level too warm during evening cooking; upper bedrooms too cold in summer; basement too cold in winter; thermostat location compromises always favored some zone over others
  • Customer priorities: Independent zone control, equipment age appropriate for major work, preserve existing equipment

Equipment Assessment

Before recommending zoning, we verified existing equipment compatibility:

  • 2008 furnace: variable-speed ECM blower ✓ (compatible with zoning)
  • 2008 AC: single-stage, will work with zoning but two-stage would perform better
  • Customer decision: keep existing equipment, install three-zone system, plan for AC upgrade in future when equipment fails

Zone Configuration

Three zones designed:

  • Zone 1 — Main level (1,200 sq ft): kitchen, living, dining, office
  • Zone 2 — Upper bedroom level (1,000 sq ft): 4 bedrooms, 2 baths
  • Zone 3 — Finished basement (1,000 sq ft): family room, guest bedroom, bath

Per-zone load analysis: – Zone 1: 14,500 BTU/h cooling / 23,000 BTU/h heating – Zone 2: 12,500 BTU/h cooling / 18,500 BTU/h heating – Zone 3: 8,000 BTU/h cooling / 13,000 BTU/h heating

Equipment Selected

  • Honeywell HZ432 zone control panel (up to 4 zones, 3 zones used)
  • Three zone dampers in main supply trunks
  • Bypass damper for excess airflow management during single-zone calls
  • Three Ecobee Smart thermostats with proper staging configuration

Project cost: $4,800

Installation

Duration: 1 day

Work performed: – Accessed existing ductwork through unfinished mechanical room areas – Cut openings in supply trunks for damper installation – Installed three zone dampers with proper sealing – Installed bypass damper between supply and return trunks – Mounted zone control panel in mechanical room – Ran low-voltage wiring to three thermostat locations – Installed three Ecobee Smart thermostats – Configured staging and zoning logic – Verified operation across all single-zone and multi-zone combinations

Commissioning

Zone operation verified across all combinations: – Zone 1 only: damper 1 open, dampers 2 & 3 closed, bypass partially open ✓ – Zone 2 only: similar pattern ✓ – Zone 3 only: similar pattern ✓ – Zones 1+2: dampers 1 & 2 open, damper 3 closed, bypass mostly closed ✓ – All zones: all dampers open, bypass fully closed ✓

Static pressure verification: – Single-zone operation: 0.45″ wc (within manufacturer max 0.5″ wc) ✓ – All zones: 0.36″ wc ✓ – Bypass operation prevents overpressure during single-zone calls

Final Cost and Customer Outcome

Customer’s cost: $4,800

Six-month customer feedback:

  • Each zone maintained at preferred temperature independently
  • Evening cooking in main level no longer affects sleeping comfort upstairs
  • Basement temperature maintained for use vs. sitting cold and unused
  • Equipment operates with longer, lower-capacity cycles producing better efficiency
  • Estimated efficiency improvement: 12-15% reduction in equipment run time
  • Three-zone control enables nighttime setback by zone (cooling bedrooms while letting main level drift)

What This Case Study Demonstrates

  • Zoning works with existing single-stage AC (though two-stage would optimize further)
  • Three-zone systems appropriate for homes with three distinct comfort areas
  • Bypass damper prevents pressure problems during single-zone calls
  • Variable-speed furnace blower essential for proper zoning operation
  • Zone-by-zone setback enables comfort customization and efficiency improvements

Considering Zoning?

If you have a Taylorsville home with multiple comfort areas, call (385) 250-0687.