Furnace Repair No Heat Call — Taylorsville Case Study

A Taylorsville customer called us at 11 AM on a December weekday morning after their furnace stopped producing heat overnight. House temperature had dropped to 60°F by morning. The 8-year-old condensing furnace was attempting to ignite but failing — the customer could hear it cycling through ignition attempts without successfully starting. This case study documents a diagnostic that traced the failure through the pressure switch back to a blocked condensate drain.

Customer Situation

  • Home: 2015-built Taylorsville two-story, approximately 2,400 sq ft
  • Existing equipment: 8-year-old Trane 96% AFUE two-stage condensing furnace
  • Symptom: Furnace cycling through ignition attempts without successful firing; no heat output
  • Severity: Cold but not severe (28°F outdoor, 60°F indoor)
  • Time of call: 11:00 AM weekday

Diagnostic Approach

Arrival: 12:50 PM (under 2-hour same-day response)

Initial observations:
– Inducer motor starting on thermostat call
– Pressure switch failing to close (verified with multimeter)
– HSI not energizing because pressure switch open
– Error code on control board: “open pressure switch”

Diagnostic measurements:
– Inducer motor amp draw: 1.0 amps (nameplate 1.2) ✓
– Pressure switch hose: connected, no obstruction visible
– Pressure switch operating threshold tested: 1.2″ wc (manufacturer spec: closes at 1.0″, opens at 0.6″)
– Actual inducer pressure: 0.7″ wc (below switch closing threshold)

Why inducer pressure was low:

Checked condensate drainage:
– Condensate drain line: visible water backup at drain trap
– Drain line obstruction: blockage approximately 18″ downstream of trap
– Result: water backing up into inducer housing area, reducing effective draft pressure
– Pressure switch correctly preventing operation under reduced draft conditions (safety system working as designed)

Root Cause and Repair

Root cause: Blocked condensate drain line caused water backup, reducing inducer pressure below switch closing threshold. Safety system correctly prevented ignition.

Repair performed:

  1. Cleared blockage from condensate drain line (used pressure flush)
  2. Inspected drain trap and cleaned biological growth
  3. Verified drain flow
  4. Replaced condensate neutralizer media (overdue maintenance)
  5. Restarted furnace
  6. Verified all measurements within specifications after restart

Combustion analysis after restart:
– CO: 11 ppm ✓
– O2: 7.8% ✓
– Combustion efficiency: 95.2% ✓
– Pressure switch closing properly
– Temperature rise: 43°F ✓

Final Cost

Customer’s invoice:
– Diagnostic visit: $99 (applied to repair)
– Drain line clearance: $185
– Neutralizer media replacement: $75
– Labor: $145
Total: $504

No equipment damage — furnace returned to full operation. Customer enrolled in maintenance plan ($189 annual) which includes annual condensate system service.

Customer Outcome

Equipment restored by 2:30 PM same day. Customer’s home temperature reached 68°F by 5 PM. Subsequent operation reliable.

Maintenance plan tune-up the following spring caught:
– Condensate neutralizer needing replacement (replaced)
– Filter loading (filter replaced)
– Minor combustion adjustment for optimal efficiency
– All findings documented in service report

What This Case Study Demonstrates

  • Symptom (no heat) traced to root cause (blocked drain) through systematic diagnostic
  • Safety system working correctly — pressure switch prevented unsafe operation
  • What we didn’t do: Replace pressure switch unnecessarily; recommend equipment replacement; bypass safety controls
  • Maintenance prevents recurrence — annual condensate service catches drain issues before they cause failures